Industrial RTU 8M NVRAM 512M DRAM
$2,540.00
Description
- Industrial PowerPC (32 bit data bus)
- Operating system: embedded LINUX
- Dynamic memory (RAM): 512 MB (478 MB Available)
- Program memory (Flash): 512 MB (272 MB for application data and programs)
- Data Logging Memory RAM: 8 MB (Battery backed)
- Datalogging: Sixnet SixLog or Red Lion Workbench
- IEC 61131 Programming: Red Lion Workbench (Sixnet ISaGRAF is supported for backward compatibility)
Power Input
- Input Voltage: 10-30 VDC
- Steady Input Current: 150 mA @ 24 V (6.2 W max.)
- Inrush: 3.0 A / 60 μs @ 24 VDC
- BTU/HR: 12.29
Switch Properties
- Operation: Unmanaged
- Number of MAC Addresses: 2
- IEEE Compliance: 802.3u, 802.3x
- Protocols: TCP/IP, ARP, UDP, IGMP, DHCP, Modbus UDP/TCP, Sixnet UDR, Modbus
- ASCII/RTU
- Latency (typical): 10 Mbps: 16 μs, 100 Mbps: 5 μs
- Switching Method: Store-and-Forward
- Maximum Throughput: 90 Mbps (Network 2)
- MDIX Auto Cable Sensing
- Auto Sensing Speed and Flow Control
- MTBF: >820,000 hours per MIL-HNDBK-217F2
Connectors
- Ethernet Ports
- Independent Networks with Unique MAC & IP Addresses
- Network 1 Port: One (1) shielded 10/100Base-T(X) port
- Network 2 Ports: Five (5) shielded 10/100Base-T(X) ports
- Serial Ports
- Supports speeds up to 115,200 baud
- RS-232 (Port A): RJ45 (TD, RD, CTS, RTS, CD, DTR, DSR, GND)
- RS-232 (Port B): RJ45 (TD, RD, CTS, RTS, CD, DTR, DSR, GND)
- RS-485 (Port C): Screw block (485+, 485-, GND) 2- wire half-duplex half-duplex, isolated 1,500 Vrms
- RS-232 (Port D): Screw block (TD, RD, RTS, CTS, GND) isolated 1,500 Vrms
- USB Port: Type B for diagnostics only
Network Media
- 10BaseT: >Cat3 cable
- 100BaseTX: >Cat5 cable
Recommended Wiring Clearance
- Front: 3″ (7.62 cm)
- Top: 2.5″ (6.35 cm)
Environmental
- Operating Temperature Range: -40 °C to 70 °C
- Storage Temperature: -40 °C to 85 °C
- Operating Humidity: 10% to 95% (non-condensing)
- Operating Altitude: 0 to 2,000 ft.
- Shock: IEC60068-2-6; Half Sine, 31 G, 11 ms duration
- Vibration: IEC60068-2-27; 9-200 Hz 2 G, 200-500 Hz 1.5 G
Certification & Compliance
- Hazardous Locations: ISA12.12.01, CSA C22.2/213, Class 1, Division 2 Groups A, B, C, D
- Electrical Safety: UL 508, CSA C22.2/142, IEC61010-1, CE
- EMI Emissions: FCC part 15, ICES-003, Class A, EN61000-6-4, CE
- EMC Immunity: EN61000-6-2, CE
- Flammability: UL 94V-0 materials
ATEX (Zone 2)
- Protection string: II 3 G Ex ec IIC T4 X
- Ambient temperature range: -20 °C ≤ Tamb ≤ 65 °C
- Use field wiring with insulation rated to at least 105 °C
- Standards evaluated for ATEX: IEC 60079-0 Edition 7.0, IEC 60079-7 Edition 5.1
- The equipment shall be installed in an enclosure that provides a degree of protection
not less than IP54 in accordance with EN/IEC 60079-7 and used in an environment
of not more than Pollution Degree 2 in accordance with EN/IEC60664-1 when
applied in Zone 2 environments. The enclosure must be accessible only by the use
of a tool.
Mechanical
- Case Dimensions:
- Height: 3.17″ (8.05 cm)
- Width: 4.75″ (12.07 cm)
- Depth: 3.00″ (7.62 cm)
- Weight: 0.75 lbs (0.34 kg)
- Mount: DIN rail 35 mm or flat panel mount